Recovery from Low-Pressure Appliances
Recover refrigerant from a low-pressure system to the Table 1 level.
11 steps5 criticalLimit 20 minAlways tested
Steps
- 1Critical stepConfirm the appliance is low-pressure (liquid saturation pressure below 45 psia at 104 F; the regulation lists R-11, R-123, R-113, R-245fa)
- 2Use a recovery machine certified under 40 CFR 82.158 for this job and follow its manufacturer's directions
- 3Put on safety glasses with side shields and gloves, work with ventilation, and avoid breathing refrigerant vapor
- 4Critical stepInspect the recovery cylinder: undamaged, rated for this refrigerant, labeled, and not holding any other refrigerant
- 5Check the cylinder's fill limit before you start: about 80 percent of capacity is the common industry and manufacturer figure (it is not set by Part 82), and your supplier or the cylinder markings may set a specific limit; watch its weight on a scale
- 6Critical stepConnect the recovery machine to the appliance and to the recovery cylinder as the machine's manufacturer directs
- 7Start the machine and recover the refrigerant, including all the liquid, until the appliance reaches 25 mm Hg absolute
- 8Critical stepIf leaks make that level unattainable, isolate leaking from non-leaking parts; take non-leaking parts to Table 1 and leaking parts as low as possible without contaminating the refrigerant, never above 0 psig
- 9Verify the level has been reached in the appliance (or the isolated part) before it is opened
- 10Close the valves and shut down the machine; do not let the recovered refrigerant escape to the air
- 11Record what you recovered and keep any records your employer or the rules require
What graders are watching for
Tips
- Low-pressure is a class defined by liquid saturation pressure below 45 psia at 104 F, not by how a particular system happens to run
- The low-pressure level is an absolute pressure: 25 mm Hg absolute for all charge sizes. The other Table 1 rows are inches Hg vacuum relative to atmospheric pressure
- For a minor repair with no evacuation to atmosphere afterward, a low-pressure appliance is pressurized to no higher than 0 psig before it is opened, instead of being pulled down to Table 1
Common mistakes
- Mixing up units, such as reading inches Hg vacuum or psig where Table 1 says mm Hg absolute.
- Applying the high-pressure numbers (0, 10 or 15 inches Hg) to a low-pressure system.
- Opening the appliance because the machine has stopped, without verifying the level.
- Using a machine not certified under 82.158, or one that cannot reach the low-pressure level.
Practice this skill
Practise the sequence in the app with critical-step highlighting and a rationale for each step.