refrigerant regulations
Refrigerant Handling and Identification
Handle refrigerant and its cylinders safely and legally.
11 steps4 criticalLimit 10 minAlways tested
Steps
- 1Confirm the refrigerant from the cylinder label and the equipment before you open anything
- 2Critical stepWear safety glasses with side shields and gloves; add goggles where liquid could spray
- 3Check the cylinder for damage, a readable label, and an overdue test date; do not use a damaged or overdue cylinder
- 4Use a refillable DOT recovery cylinder for recovered refrigerant, never a disposable one
- 5Use recovery or recycling equipment certified for that refrigerant and appliance
- 6Use hoses, gauges and fittings made for the refrigerant and its pressure; never force a connection
- 7Critical stepOpen valves slowly and check the hookup as you go
- 8Critical stepDo not knowingly vent refrigerant, including after you recover it
- 9Never mix refrigerants in a system or a cylinder
- 10Leak test with nitrogen, using a pressure regulator and relief valve, never oxygen or compressed air; do not pressurize a system with refrigerant
- 11Close valves and keep the cap on when you finish; store the cylinder upright, secured, cool and out of the sun
What graders are watching for
Tips
- Never knowingly release refrigerant. De minimis releases are excused only when they come from good-faith recovery or recycling and the applicable practices are followed and certified recovery equipment is used (40 CFR 82.154(a)(2)).
- Pressure rating matters: higher-pressure refrigerants need hoses, gauges and tools made for them. Equipment makers publish tools specified for the refrigerant (for example, R410A-specific manifolds and hoses).
- Exam recall: recovery cylinders are refillable, DOT approved, yellow and gray; disposable cylinders are never refilled; EPA lists the risks of filling a cylinder more than 80 percent full; use nitrogen, not oxygen or compressed air, for leak detection.
Common mistakes
- Going by cylinder color instead of the label.
- Releasing a small amount to clear a hose or bleed a line; only good-faith releases while following the recovery rules are excused.
- Recovering into a disposable cylinder or filling a cylinder past 80 percent full.
- Using a hose or gauge not made for the refrigerant's pressure.
Practice this skill
Practise the sequence in the app with critical-step highlighting and a rationale for each step.