Refrigerant Recovery from Stationary Equipment

Remove refrigerant from a stationary appliance into an external cylinder so it can be opened without release.

12 steps5 criticalLimit 30 minAlways tested

Steps

  1. 1Know the refrigerant and the appliance's full charge, and turn off power to the system
  2. 2Critical stepWork out the pressure class (from the refrigerant) and use class and full charge to find the Table 1 level you must reach
  3. 3Use a recovery machine certified under 40 CFR 82.158, and follow its manufacturer's directions
  4. 4Put on safety glasses with side shields and gloves, and work with ventilation, away from low spots where vapor collects
  5. 5Critical stepInspect the recovery cylinder: undamaged, rated for this refrigerant, labeled with the refrigerant, and never mixed with another
  6. 6Check the cylinder's fill limit before you start: about 80 percent of capacity is the common industry and manufacturer figure (it is not set by Part 82), and your supplier or the cylinder markings may set a specific limit; watch its weight on a scale
  7. 7Critical stepConnect the recovery machine to the appliance's high-side and low-side service ports with a manifold, and to the recovery cylinder
  8. 8Critical stepStart the machine and recover all the refrigerant, liquid included, while watching the cylinder weight
  9. 9Critical stepKeep recovering until the Table 1 level is reached; if leaks make it unattainable, isolate the leaking part and take it as low as possible without contaminating the refrigerant, never above 0 psig
  10. 10Verify the level has been reached in the appliance (or the isolated part) before it is opened
  11. 11Close the valves and shut down the machine; do not let the recovered refrigerant escape to the air
  12. 12Record what you recovered and keep any records your employer or the rules require

What graders are watching for

Tips
  • Table 1 of 40 CFR 82.156(a) sets the level by pressure class and full charge; small appliances instead use percent recovery or 4 inches Hg vacuum
  • Do not mix refrigerants in a recovery cylinder, and label it with the refrigerant it holds
  • Recovered refrigerant may go back into the same appliance or another one owned by the same person; selling it to a new owner requires reclamation by an EPA-certified reclaimer

Common mistakes

  • Using one flat number for every system. The level depends on class and charge, and low-pressure uses a different unit (mm Hg absolute).
  • Mixing up 10 and 15 inches Hg. Medium-pressure at 200 lb or more is 15; high-pressure at 200 lb or more is 10.
  • Applying the large-appliance table to a small appliance, or the reverse.
  • Opening the system because the machine stopped, without confirming the reading.