Charging by Weight (Cylinder Method)

Put a measured amount of refrigerant into a system with the cylinder on a scale.

13 steps5 criticalLimit 15 minAlways tested

Steps

  1. 1Critical stepLeak test and evacuate the system first so air and moisture are out before you charge it
  2. 2Confirm the refrigerant the equipment calls for and that the cylinder label matches; use no other refrigerant
  3. 3Check the cylinder and its valve for damage, and use a manifold and hoses made for the refrigerant and its pressure
  4. 4Connect the manifold and hoses with the cylinder on an electronic scale; never force a connection
  5. 5Zero the scale as the scale maker directs
  6. 6Critical stepFind the charge amount and method in the equipment manufacturer's data: by weight, superheat or subcooling
  7. 7Critical stepFor a blend such as R-410A, charge liquid: invert a standard cylinder, or use a dip-tube cylinder upright
  8. 8Where vapor would normally be charged into a running system, put a metering valve in the charging line so the liquid flashes to vapor (Arkema, for R-410A); never let liquid reach the compressor
  9. 9Critical stepOpen valves slowly and watch the scale and gauges
  10. 10Stop at the specified weight; do not overcharge
  11. 11Close the cylinder and manifold valves, then disconnect without venting refrigerant
  12. 12Run the system and check operating readings against the manufacturer's figures
  13. 13Record the refrigerant type and amount added where required (for appliances with a full charge of 50 or more pounds of class I or II refrigerant, 40 CFR 82.157, in which case the owner also gets documentation) and under your employer's rules

What graders are watching for

Tips
  • For blends, charge liquid, not vapor. A manufacturer notes that taking vapor from the cylinder can change the blend's composition and lower efficiency.
  • Weight is not the only measure. Manufacturers set the charge by superheat, subcooling or weight depending on the system and its metering device, so follow the equipment's own manual.
  • Exam recall for low-pressure (Type III) recharging: introduce vapor before liquid to prevent freezing of water in the tubes, and charge centrifugals through the evaporator charging valve.

Common mistakes

  • Charging a system that was never evacuated or leak tested.
  • Using a different refrigerant than the equipment calls for.
  • Forgetting to zero the scale, so the weight added is wrong.
  • Charging vapor from a blend cylinder, which can shift the blend.