equipment service
Major Component Replacement
Take the refrigerant out, open the circuit, swap the part and restore the system.
12 steps4 criticalLimit 60 min
Steps
- 1Find the Table 1 evacuation level for this appliance from its refrigerant pressure class and full charge (small appliances use the separate percent-recovery rule in 82.156(b))
- 2Critical stepDecide whether to recover the whole appliance or only the part, and isolate the part with its service valves if its refrigerant can be isolated to a system receiver
- 3Critical stepRecover the refrigerant, liquid included, with certified recovery equipment down to the Table 1 level; do not vent
- 4Verify the required level has been reached before opening the appliance
- 5If leaks keep you from reaching the level, isolate leaking from non-leaking parts and take the leaking part as low as you can without contaminating the refrigerant, not above 0 psig
- 6Remove the failed component
- 7Install the new component, following the manufacturer's instructions for gaskets, torque and brazing
- 8Critical stepIf brazing, flow dry nitrogen through the joint while heating
- 9Critical stepPressure test the new joints with nitrogen and check them for leaks before evacuating
- 10Evacuate the system to the vacuum level the manufacturer specifies to remove air and moisture before charging
- 11Charge the system as the manufacturer specifies and check that it runs correctly
- 12Record the part replaced, the refrigerant recovered and the refrigerant added; on appliances of 50 lb or more, record the date, parts, work done, person, and refrigerant added
What graders are watching for
Tips
- You may not knowingly vent refrigerant while servicing an appliance. Recover first; nitrogen is the exempt gas, refrigerant is not.
- Removing a compressor, condenser, evaporator or auxiliary heat exchange coil is major repair, as is uncovering an opening of more than 4 square inches of flow area for more than 15 minutes. The 0 psig shortcut applies only to repairs that are not major, and only when the appliance is not to be evacuated to the atmosphere afterward.
- Moisture left in the system can form acids that damage the compressor, which is why the system is evacuated before charging.
Common mistakes
- Opening the system before recovery is verified.
- Venting the isolated section to speed things up.
- Treating a compressor swap as minor repair and stopping at 0 psig.
- Brazing with no nitrogen flow.