equipment service
Dehydration of Wet Systems
Remove moisture from a system that has been opened or contaminated.
9 steps3 criticalLimit 60 min
Steps
- 1Make sure the refrigerant has been recovered to the required level (Table 1, or the leak and minor-repair allowances in 82.156), and verified, before the system is opened; venting is prohibited, so dehydration is never done by venting
- 2Find out how the moisture got in: building or opening the system, a suction-side leak while under vacuum, wet oil or refrigerant, or a water-cooled condenser leak
- 3Critical stepRepair the leak or fix the cause so moisture cannot get back in
- 4Replace the filter-drier whenever the system has been opened or a main component replaced; never reuse a used drier
- 5Connect a vacuum pump with a blank-off (isolation) valve through vacuum-rated lines to both sides, and a micron gauge that reads the system
- 6Pull a deep vacuum with the pump until the micron gauge reaches the target from the manufacturer or your procedure (sources differ: JB Industries calls a system that holds under 500 microns complete)
- 7Critical stepIf your procedure calls for a staged evacuation, break the vacuum with dry nitrogen between pulls and pull again, as that procedure directs (EPA GreenChill's commercial procedure does this)
- 8Close the isolation valve and watch the micron gauge: a slow rise points to moisture still in the system, a rapid rise toward atmospheric pressure points to a leak
- 9Repeat until the vacuum holds, then break it with the refrigerant to be charged and charge as the manufacturer specifies
What graders are watching for
Tips
- Moisture in a refrigeration system can block the expansion device with ice, corrode metal parts, damage the insulation in hermetic compressors and break the oil down into acid
- A filter-drier removes moisture left after evacuation or that enters later; Danfoss says never to reuse a used drier, because it can give moisture back off
- A deep vacuum measured on a micron gauge is the way to tell whether a system is dry and free of leaks; a compound gauge cannot show it
Common mistakes
- Starting before recovery is complete, which means venting refrigerant.
- Reusing the old filter-drier, leaving saturated desiccant in the circuit.
- Charging before checking that the vacuum holds, so a leak or leftover moisture is sealed in.
- Stopping the vacuum early because the pump has run a while, rather than because the micron reading is low and steady.
Practice this skill
Practise the sequence in the app with critical-step highlighting and a rationale for each step.
Start your 7-day free trial7 days free, then $9.99/month. Cancel anytime.